8.3 Recommended port connections

Field experience and extensive laboratory tests carried out by SWEP R&D department have shown that the size of the connections and pipes on the refrigerant side of the brazed plate heat exchanger can have an important effect on the performance of the brazed plate heat exchanger and the system in total. Selecting the correct connections and corresponding pipes can help to improve the performance and stabilize the evaporation process.

Evaporation is a complicated two-phase process where the two-phase fluid must be evenly distributed over the channels as well as over the plate itself. Great efforts have been made to optimize efficiency with special plate patterns and distribution devices. Figure 8.21 shows the brazed plate heat exchanger and the immediate components, i.e. connections and pipes, mentioned in the text.

Evaporator inlet pipe and connection (F3)

SWEP's distribution device is most effective when liquid and vapor are a homogeneous mixture at the entrance of the brazed plate heat exchanger. Directly after the expansion valve, vapor and liquid are completely mixed. They will stay in this homogeneous form for a reasonable time provided the flow velocity is high enough to create the necessary turbulence. If the velocity is too low, i.e. the pipe dimension is too large, phase separation will occur more quickly. The refrigerant flow into the evaporator then becomes divided into one fast vapor stream and one slower liquid stream, giving less predictable performance. Using a pipe that is too small induces unnecessarily high pressure drop and results in energy losses.

The expansion valve should normally be placed 150-300 mm from the inlet. However, with correctly dimensioned piping, the distance can be increased without large losses of performance. Figure 8.22 shows the recommended position of the expansion valve relative to the inlet port of a SWEP brazed plate heat exchanger evaporator. The best position is at the same level as the evaporator inlet which result in a horizontal pipe between expansion valve and evaporator inlet. The performance of SWEP evaporators are generally evaluated in this horizontal setup and performance prediction is therefore most accurate. If this positioning is not possible, the expansion valve should be installed higher than the evaporator inlet. SWEP do not recommend to install the expansion valve lower than the inlet.

In Figure 8.23 the suggested pipe and connection setup are shown. The inlet connection selected should never be larger than the inlet port diameter of the F3 port, because this increases the risk of phase separation. Recommended dimension for the inlet pipes and F3 connections depends on the case but in general it is beneficial to have an inlet vapor/liquid velocity of 10-25 m/s. Due to the distribution device, the inlet port size (F3) is smaller in a dedicated evaporator than in a B-model.

Different solutions for the soldered evaporator inlet connection have different consequences:

  • A small inner diameter will lead to increased vapor and liquid velocities.
  • A large pipe connected to a smaller inner diameter inlet will help to return liquid and vapor to a homogeneous mixture, if done close to the expansion valv.

Evaporator outlet pipe and connection (F1)

The refrigerant vapor leaving the evaporator should have sufficient velocity to carry the small volume of compressor oil circulating in the system. Otherwise, the oil will accumulate and adhere to the channel walls and dramatically reduce the heat transfer coefficient. This results in a lower evaporation temperature and reduced system capacity.

If the velocity on the suction side of the brazed plate heat exchanger becomes high, the induced pressure drop can cause problems. In the suction pipe, velocities above 25 m/s will lead to energy losses, thus lowering the total COP for the system. If the port velocity becomes too high, the induced port pressure drop will cause maldistribution of refrigerant inside the brazed plate heat exchanger. A large pressure drop will also amplify the pressure difference over the plate pack, increasing the risk of boiling instability.

A further increase in the connection and suction pipe dimensions will reduce the pressure drop in the suction pipe. However, the risk of maldistribution and instability problems in the evaporator remains. SWEP recommends changing to a larger model, using double vapor exits or oversurfacing the brazed plate heat exchanger to compensate for the decreased efficiency.

Figure 8.24 shows outlet connection and piping variations. Versions (d) and (f) are considered immediately unsuitable. In version (d), an unnecessary constriction is induced, which could cause pulsations in the evaporator if the port velocity is high. Versions (b) or (e) are suggested instead. Version (f) has a large connection but a reduced pipe that will increase the flow velocity in the suction pipe. Versions (b) or (c) are recommended instead. Versions (a) and (e) may be unsuitable, depending on the system design. If calculations show that connection and pipe velocities are above 25 m/s, an increased pipe size will decrease energy losses. However, there is still a risk of maldistribution. Designing a larger brazed plate heat exchanger or two vapor exits will decrease the port velocity. In version (e), the pipe is also reduced, which will increase the velocity, and the fitting will induce an extra pressure drop.

Conclusion: The inlet and outlet velocities affect the evaporation performance and the stability of the evaporator. Maldistribution, which will reduce performance and cause instability, is magnified by:

  • Separated vapor and liquid flows in the inlet pipe, caused by low velocity and/or unsuitable piping design.
  • High pressure-drop in the outlet port, caused by high vapor velocity.

By choosing the correct refrigeration side connections, the performance and stability of evaporation can be improved.

<< back | next​​​​​​​ >>